    Sycor Part No AWGStrandingInsulation Thickness (In)Nom. O.D. (In)TempVoltage RatingCSA StyleApprox Weight LBS./MFTAmpacity (dry)
    A2K1401B 14Solid0.030.124-40°C to 90°C600CSA RW901735
    A2K1407B 1470.030.131-40°C to 90°C600CSA RW901735
    A2K1201B 12Solid0.030.141-40°C to 90°C600CSA RW902540
    A2K1207B 1270.030.148-40°C to 90°C600CSA RW902540
    A2K1001B 10Solid0.030.162-40°C to 90°C600CSA RW903755
    A2K1007B 1070.030.173-40°C to 90°C600CSA RW903855
    A2K0807B 870.0450.235-40°C to 90°C600CSA RW906380
    A2K0607B 670.0450.271-40°C to 90°C600CSA RW9096105
    A2K0407B 470.0450.318-40°C to 90°C600CSA RW90147140
    A2K0307B 370.0450.345-40°C to 90°C600CSA RW90183165
    A2K0207B 270.0450.376-40°C to 90°C600CSA RW90228190
    A2K0119B 1190.0550.435-40°C to 90°C600CSA RW90288220
    A2K1/019B 1/0190.0550.475-40°C to 90°C600CSA RW90359260
    A2K2/019B 2/0190.0550.518-40°C to 90°C600CSA RW90447300
    A2K3/019B 3/0190.0550.567-40°C to 90°C600CSA RW90558350
    A2K4/019B 4/0190.0550.623-40°C to 90°C600CSA RW90698405
    A2K250M37B 250 MCM370.0650.691-40°C to 90°C600CSA RW90827455
    A2K300M37B 300 MCM370.0650.744-40°C to 90°C600CSA RW90986500
    A2K350M37B 350 MCM370.0650.794-40°C to 90°C600CSA RW901145570
    A2K400M37B 400 MCM370.0650.839-40°C to 90°C600CSA RW901303615
    A2K500M37B 500 MCM370.0650.943-40°C to 90°C600CSA RW901621700
    A2K600M61B 600 MCM610.081.053-40°C to 90°C600CSA RW901950780
    A2K750M61B 750 MCM610.081.158-40°C to 90°C600CSA RW902424885
    A2K1000M61B 1000 MCM610.081.312-40°C to 90°C600CSA RW9032111055

    24 Items

    Additional strandings and gauges available upon request. Please contact us to enquire.
    Replace suffix “B” with “A” for an aluminum conductor.

    Download Spec Sheet                 

     

    CSA RW90 Wire 90°C, 600 Volts

      

      

    Stranded CSA RW90 Wire

    Solid CSA RW90 Wire

    Description of CSA RW90 Wire:

    The RW90 wire consists of a single, soft-drawn copper conductor, surrounded by a low-temperature, moisture-resistant cross-linked polyethylene (XLPE) insulation. RW90 is acceptable for use in open wiring applications and raceways (except ventilated cable trays and ventilated flexible cable trays) in both dry and wet locations. The RW90 wire is available in either 600V or 1kV and boasts a temperature range of -40°C to 90°C. RW90 is also approved for usage in ceiling fixtures. While the standard black jacket its sunlight-resistant, RW90 wire in coloured insulations are not. 

    Construction of CSA RW90 Wire:

    Stranded or solid annealed bare copper conductor (aluminum available)
    Cross-Linked Polyethylene (XLPE) insulation

       

    Temperature Rating of CSA RW90 Wire:

    -40°C to 90°C

       

    Approvals of CSA RW90 Wire:

    CSA RW90
    Flame Test FT-4

    Voltage Rating of CSA RW90 Wire:

    600 Volts (1000V construction available)

      

    Application of CSA RW90 Wire:

    The RW90 wire is a single conductor wire with standard sunlight resistant black XLP insulation, which also has low-temperature and moisture resistance. The RW90 building wire is approved for ceiling fixtures and is resistant to weathering.

    Colour options for RW90 Wire:

    Black Colour 0Brown Colour 1Red Colour 2Orange Colour 3Yellow Colour 4Green Colour 5Blue Colour 6Violet Colour 7Grey Colour 8White Colour 9

      

    Value-Added Services for RW90 Wire:

    Resppol VASStripe VASTwist VASCut & Strip VASTerminate VAS

    ROHS stand compliant

      

    All specifications are provided for reference only. Specifications will vary between manufacturers and are subject to change without notice. Be sure to check with your sales rep for the most accurate and up to date information when ordering.