Toggle Nav
rfq-icon
mobile icon
Close
  • Menu
  • Setting

MV-90 XLPE Insulated, PVC Jacketed 35 kV Copper Tape Shielded

12 Items

per page
Set Descending Direction

MV-90 XLPE Insulated, PVC Jacketed 35 kV Copper Tape Shielded

    Sycor Part No AWGStrandingConductor Diameter (in)TempVoltage RatingUL Style100% NOM. Diam. Over Insul.100% Jacket Thickness100% Approx Weight Copper100% Approx Weight Alum.133% NOM. Diam. Over Insul.133% Jacket Thickness133% Appr. O.D (in)133% Approx Weight Copper133% Approx Weight Alum.
    MV9035KT100-1/0 1/0190.3490°C 35kV10721.068010227951.21801.491176949
    MV9035KT100-2/0 2/0190.3890°C 35kV10721.108011398531.25801.5312961010
    MV9035KT100-3/0 3/0190.4290°C 35kV10721.158012849231.30801.5714461085
    MV9035KT100-4/0 4/0190.4890°C 35kV10721.2080146110061.35801.6316271173
    MV9035KT100-250 250 MCM370.5290°C 35kV10721.2680162310851.411101.7418971359
    MV9035KT100-300 300 MCM370.5790°C 35kV10721.3180181711721.461101.7920981454
    MV9035KT100-350 350 MCM370.6290°C 35kV10721.3580200912551.501101.8422971544
    MV9035KT100-400 400 MCM370.6690°C 35kV10721.3980219713371.541101.9125411681
    MV9035KT100-500 500 MCM370.7490°C 35kV10721.47110267415981.621101.9929261850
    MV9035KT100-600 600 MCM610.8190°C 35kV10721.56110310718161.711102.0833202029
    MV9035KT100-750 750 MCM610.9190°C 35kV10721.65110365320401.801102.1738752262
    MV9035KT100-1000 1000 MCM611.0690°C 35kV10721.81110455924091.961102.3247952645

    12 Items

    per page
    Set Descending Direction

    Available in 100% and 133% insulation levels. Please contact us to enquire.

    Download Spec Sheet

        

    Description - MV-90 XLPE Insulated, PVC Jacketed 35 kV Copper Tape Shielded:

    Medium voltage shielded power cable.

      

    Approvals - MV-90 XLPE Insulated, PVC Jacketed 35 kV Copper Tape Shielded:

    UL listed as MV-90
    UL 1072
    ICEA S-93/639/NEMA WC74-STD 5kV-40 Kv SPC
    ICEA S-97-682- SPC
    AEIC CS8 ED - SPC

      

    Construction - MV-90 XLPE Insulated, PVC Jacketed 35 kV Copper Tape Shielded:

    • Soft annealed bare copper conductor, Class B per ASTM B496.
    • Semi conducting cross-linked polyethylene (XLPE) conductor shield.
    • XLPE insulation.
    • Soft annealed uncoated copper tape, 5 mil thick, 25% min overlap metallic shield.
    • Semi conducting cross-linked polyethylene (XLPE) insulation.
    • Oil Resistant, sunlight resistant and flame retardant Polyvinyl Chloride (PVC) compound jacket.

    Temperature Rating - MV-90 XLPE Insulated, PVC Jacketed 35 kV Copper Tape Shielded: 

    90°C- Normal Operating Temperature

      

    Voltage Rating - MV-90 XLPE Insulated, PVC Jacketed 35 kV Copper Tape Shielded:

    35kV 100% and 133%

      

    Application - MV-90 XLPE Insulated, PVC Jacketed 35 kV Copper Tape Shielded:

    Primary power and distribution circuits in industrial and commercial installations. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.
    Power circuits in generating plants where line to ground fault current are within shield capabilities.
    May be used in wet or dry locations, installed in cable trays, raceways, duct and open air, aerially or directly buried as permitted by NEC.

    All specifications are provided for reference only. Specifications will vary between manufacturers and are subject to change without notice. Be sure to check with your sales rep for the most accurate and up to date information when ordering.