MV90 5kV Copper Tape Shield, XLPE Insulated, PVC Jacketed
MV90 5kV Copper Tape Shield, XLPE Insulated, PVC Jacketed
Sycor Part No | AWG | Stranding | Conductor Diameter (in) | Temp | Voltage Rating | UL Style | 100% Insulation Thickness | 100% Jacket Thickness | 100% Approx Weight Copper | 100% Approx Weight Alum. | 133% Insulation Thickness | 133% Jacket Thickness | 133% Appr. O.D (in) | 133% Approx Weight Copper | 133% Approx Weight Alum. | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
MV905KT100-8 | 8 | 7 | 0.13 | 90°C | 5kV | 1072 | 0.35 | 60 | 200 | - | 0.35 | 60 | 0.56 | 200 | - |
|
MV905KT100-6 | 6 | 7 | 0.17 | 90°C | 5kV | 1072 | 0.38 | 60 | 245 | 188 | 0.38 | 60 | 0.59 | 245 | 188 |
|
MV905KT100-4 | 4 | 7 | 0.21 | 90°C | 5kV | 1072 | 0.43 | 60 | 311 | 221 | 0.43 | 60 | 0.64 | 311 | 221 |
|
MV905KT100-2 | 2 | 7 | 0.27 | 90°C | 5kV | 1072 | 0.48 | 60 | 410 | 267 | 0.48 | 60 | 0.69 | 410 | 267 |
|
MV905KT100-1 | 1 | 19 | 0.30 | 90°C | 5kV | 1072 | 0.51 | 60 | 475 | 295 | 0.51 | 60 | 0.72 | 475 | 295 |
|
MV905KT100-1/0 | 1/0 | 19 | 0.34 | 90°C | 5kV | 1072 | 0.55 | 60 | 558 | 331 | 0.55 | 60 | 0.76 | 558 | 331 |
|
MV905KT100-2/0 | 2/0 | 19 | 0.38 | 90°C | 5kV | 1072 | 0.59 | 60 | 659 | 373 | 0.59 | 60 | 0.80 | 659 | 373 |
|
MV905KT100-3/0 | 3/0 | 19 | 0.42 | 90°C | 5kV | 1072 | 0.64 | 80 | 821 | 460 | 0.64 | 80 | 0.89 | 821 | 460 |
|
MV905KT100-4/0 | 4/0 | 19 | 0.48 | 90°C | 5kV | 1072 | 0.69 | 80 | 980 | 526 | 0.69 | 80 | 0.94 | 980 | 526 |
|
MV905KT100-250 | 250 MCM | 37 | 0.52 | 90°C | 5kV | 1072 | 0.75 | 80 | 1124 | 586 | 0.75 | 80 | 0.99 | 1124 | 586 |
|
MV905KT100-350 | 350 MCM | 37 | 0.62 | 90°C | 5kV | 1072 | 0.84 | 80 | 1477 | 724 | 0.84 | 80 | 1.09 | 1477 | 786 |
|
MV905KT100-500 | 500 MCM | 37 | 0.74 | 90°C | 5kV | 1072 | 0.96 | 80 | 1996 | 921 | 0.96 | 80 | 1.21 | 1996 | 921 |
|
MV905KT100-750 | 750 MCM | 61 | 0.91 | 90°C | 5kV | 1072 | 1.14 | 80 | 2879 | 1266 | 1.14 | 80 | 1.41 | 2879 | 1266 |
|
MV905KT100-1000 | 1000 MCM | 61 | 1.06 | 90°C | 5kV | 1072 | 1.30 | 80 | 3723 | 1573 | 1.30 | 80 | 1.57 | 3723 | 1573 |
|
Available in 100% and 133% insulation levels. Please contact us to enquire.
Description of MV90 5kV Copper Tape Shield:
The MV90 5kV Copper Tape Shield is a medium voltage shielded power cable.
Approvals of MV90 5kV Copper Tape Shield:
UL listed as MV-90
UL1072
Shielded power cables 5,000 to 46,000V
5 kV 100% and 133% insulation levels
ICEA S-97-682: utility
shielded power cables 5,000 to 46,000V
AEIC CS8: extruded dielectric shielded
Power cables 5,000 to 46,000V
Construction of MV90 5kV Copper Tape Shield:
- Soft annealed bare copper conductor, Class B per ASTM B496.
- Semiconducting cross-linked polyethylene (XLPE) conductor shield.
- XLPE insulation.
- Semiconducting cross-linked polyethylene (XLPE) insulation.
- Soft annealed uncoated copper tape, 5 mil thick, 25% min overlap metallic shield.
- Oil Resistant, sunlight resistant and flame retardant Polyvinyl Chloride (PVC) compound jacket.
Application of MV90 5kV Copper Tape Shield:
The MV90 5kV Copper Tape Shield cable is typically used for primary power and distribution circuits in industrial and commercial installations. Power circuits in generating plants where line to ground fault currents are within shield capabilities. May be used in wet or dry locations, installed in cable trays, raceways, duct and open-air, aerially or directly buried as permitted by NEC.
Temperature Rating of MV90 5kV Copper Tape Shield:
90°C- Normal Operating Temperature
Voltage Rating of MV90 5kV Copper Tape Shield:
5kV 100% and 133%
All specifications are provided for reference only. Specifications will vary between manufacturers and are subject to change without notice. Be sure to check with your sales rep for the most accurate and up to date information when ordering.