    Sycor Part No AWGStrandingConductor Diameter (in)TempVoltage RatingUL Style100% Insulation Thickness100% Jacket Thickness100% Approx Weight Copper100% Approx Weight Alum.133% Insulation Thickness133% Jacket Thickness133% Appr. O.D (in)133% Approx Weight Copper133% Approx Weight Alum.
    MV905KT100-8 870.1390°C 5kV10720.3560200-0.35600.56200-
    MV905KT100-6 670.1790°C 5kV10720.38602451880.38600.59245188
    MV905KT100-4 470.2190°C 5kV10720.43603112210.43600.64311221
    MV905KT100-2 270.2790°C 5kV10720.48604102670.48600.69410267
    MV905KT100-1 1190.3090°C 5kV10720.51604752950.51600.72475295
    MV905KT100-1/0 1/0190.3490°C 5kV10720.55605583310.55600.76558331
    MV905KT100-2/0 2/0190.3890°C 5kV10720.59606593730.59600.80659373
    MV905KT100-3/0 3/0190.4290°C 5kV10720.64808214600.64800.89821460
    MV905KT100-4/0 4/0190.4890°C 5kV10720.69809805260.69800.94980526
    MV905KT100-250 250 MCM370.5290°C 5kV10720.758011245860.75800.991124586
    MV905KT100-350 350 MCM370.6290°C 5kV10720.848014777240.84801.091477786
    MV905KT100-500 500 MCM370.7490°C 5kV10720.968019969210.96801.211996921
    MV905KT100-750 750 MCM610.9190°C 5kV10721.1480287912661.14801.4128791266
    MV905KT100-1000 1000 MCM611.0690°C 5kV10721.3080372315731.30801.5737231573

    14 Items

    per page
    Set Descending Direction

    Available in 100% and 133% insulation levels. Please contact us to enquire.

    Download Spec Sheet

    MV90 XLPE Insulated, PVC Jacketed 5kV Copper Tape Shield  


    Description - MV90 5kV Copper Tape Shield:

    Medium voltage shielded power cable.

      

    Approvals - MV90 5kV Copper Tape Shield:

    UL listed as MV-90                                             
    UL 1072                                               
    Shielded power cables 5,000 to 46,000V     
    5 kV 100% and 133% insulation levels
    ICEA S-97-682: utility                                        
    shielded power cables 5,000 to 46,000V      
    AEIC CS8: extruded dielectric shielded
    Power cables 5,000 to 46,000V

     

    Construction - MV90 5kV Copper Tape Shield:

    • Soft annealed bare copper conductor, Class B per ASTM B496.
    • Semi conducting cross-linked polyethylene (XLPE) conductor shield.
    • XLPE insulation.
    • Semi conducting cross-linked polyethylene (XLPE) insulation.
    • Soft annealed uncoated copper tape, 5 mil thick, 25% min overlap metallic shield.
    • Oil Resistant, sunlight resistant and flame retardant Polyvinyl Chloride (PVC) compound jacket.

    Temperature Rating - MV90 5kV Copper Tape Shield:

    90°C- Normal Operating Temperature

      

    Voltage Rating - MV90 5kV Copper Tape Shield:

    5kV 100% and 133%

      

    Application - MV90 5kV Copper Tape Shield:

    Primary power and distribution circuits in industrial and commercial installations. Power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry locations, installed in cable trays, raceways, duct and open air, aerially or directly buried as permitted by NEC.

    ROHS stand compliant

    All specifications are provided for reference only. Specifications will vary between manufacturers and are subject to change without notice. Be sure to check with your sales rep for the most accurate and up to date information when ordering.