MV90 5kV Wire Shielded, XLPE Insulated, PVC Jacketed

13 Items

Set Descending Direction

MV90 5kV Wire Shielded, XLPE Insulated, PVC Jacketed

Download Spec Sheet                                                     More info!

Share

    Sycor Part No AWGStrandingConductor NOM. O.D.TempVoltage RatingUL Style100% NOM. Diam. Over Insul.100% Jacket Thickness100% Approx Weight Copper100% Approx Weight Alum.133% NOM. Diam. Over Insul.133% Jacket Thickness133% Appr. O.D (in)133% Approx Weight Copper133% Approx Weight Alum.
    MV905KS100-6 670.1790°C5kV10720.17602291720.17600.63229172
    MV905KS100-4 470.2190°C5kV10720.43602912020.43600.68291202
    MV905KS100-2 270.2790°C5kV10720.48603922500.48600.73392250
    MV905KS100-1 1190.3090°C5kV10720.51604552750.51600.76455275
    MV905KS100-1/0 1/0190.3490°C5kV10720.55605353080.55600.80535308
    MV905KS100-2/0 2/0190.3890°C5kV10720.59806683820.59800.88668382
    MV905KS100-3/0 3/0190.4290°C5kV10720.64807934330.64800.93793433
    MV905KS100-4/0 4/0190.4890°C5kV10720.69809494940.69800.98949494
    MV905KS100-250 250 MCM370.5290°C5kV10720.758010965590.75801.031096559
    MV905KS100-350 350 MCM370.6290°C5kV10720.848014436890.84801.131443689
    MV905KS100-500 500 MCM370.7490°C5kV10720.968019528770.96801.251952877
    MV905KS100-750 750 MCM610.9190°C5kV10721.1480282812151.14801.4528281215
    MV905KS100-1000 1000 MCM611.0690°C5kV10721.3080366015101.30801.6136601510

    13 Items

    Set Descending Direction

    *Available in 100% and 133% Insulation Levels.  

    Download Spec Sheet  

    MV90 XLPE Insulated, PVC Jacketed 5kV Wire Shielded Cable 

      

    Description of MV90 5kV Wire Shielded:

    The MV90 5kV Wire Shielded cable is a designated medium voltage shielded power cable.

    Approvals - MV90 5kV Wire Shielded:

    UL listed as MV-90                                             
    UL1072                                                                               
    ICEA S-93-639/NEMA WC74:                          
    Shielded power cables 5,000 to 46,000V
    ICEA S-97-682: utility                                        
    Shielded power cables 5,000 to 46,000V     
    AEIC CS8: extruded dielectric shielded
    Power cables 5,000 to 46,000V

      

    Construction - MV90 5kV Wire Shielded:

    • Stranded, soft annealed bare copper conductor
    • (Aluminum conductor available upon request)
    • Semi-conducting cross-linked polyethylene (XLPE) conductor shield
    • Solid, soft annealed bare copper, helically applied and uniformly spaced, binder tape
    • Semi-conducting cross-linked Polyethylene (XLPE) insulation
    • Black oil & sunlight resistant and flame retardant thermoplastic Polyvinyl Chloride (PVC) jacket

    Application - MV90 5kV Wire Shielded:

    The MV90 5kV Wire Shielded cable is typically used for primary power and distribution circuits in industrial and commercial installations. Power circuits in generating plants where a line ground-fault current is within shield capabilities. May be used in wet or dry locations, installed in cable trays, raceways, ducts and open-air, aerially or directly buried as permitted by NEC.

    Temperature Rating - MV90 5kV Wire Shielded:

    Normal Operating Temperature - 90°C

      

    Voltage Rating - MV90 5kV Wire Shielded:

    5kV 100% and 133% IL

    ROHS stand compliant

    All specifications are provided for reference only. Specifications will vary between manufacturers and are subject to change without notice. Be sure to check with your sales rep for the most accurate and up to date information when ordering.