    Sycor Part No AWGStrandingConductor NOM. O.D.TempVoltage RatingUL Style100% Insulation Thickness100% Approx Weight Copper100% Approx Weight Alum.
    MV902.4K100-8 870.1390°C2.4 kV107211094-
    MV902.4K100-6 670.1790°C2.4 kV107211013174
    MV902.4K100-4 470.2190°C2.4 kV107211018797
    MV902.4K100-2 270.2790°C2.4 kV1072110273131
    MV902.4K100-1 1190.3090°C2.4 kV1072110331151
    MV902.4K100-1/0 1/0190.3490°C2.4 kV1072110405178
    MV902.4K100-2/0 2/0190.3890°C2.4 kV1072110498212
    MV902.4K100-3/0 3/0190.4290°C2.4 kV1072110614254
    MV902.4K100-4/0 4/0190.4890°C2.4 kV1072110760305
    MV902.4K100-250 250 MCM370.5290°C2.4 kV1072120898361
    MV902.4K100-350 350 MCM370.6290°C2.4 kV10721201227474
    MV902.4K100-500 500 MCM370.7490°C2.4 kV10721201715641
    MV902.4K100-750 750 MCM610.9190°C2.4 kV10721302539928
    MV902.4K100-1000 1000 MCM611.0690°C2.4 kV107213033441197

    14 Items

    Set Descending Direction

    *Available in 100% and 133% Insulation Levels.

    Download Spec Sheet 

    MV90 XLPE Insulated 2.4kV Non Shielded   

      

    Description - MV90 2.4kV Non-Shielded:

    The MV90 2.4kv is a designated medium voltage power cable.

    Temperature Rating - MV90 2.4kV Non-Shielded:

    90°C – Normal Operating Temperature

      

    Voltage Rating - MV90 2.4kV Non-Shielded:

    2.4 kV per UL
    5 kV 100% and 3 kV133% per ICEA

      

    Application - MV90 2.4kV Non-Shielded:

    The MV90 2.4kv is typically used for primary power and distribution circuits in industrial and commercial installations, for use in wet or dry locations.
    Per NEC, use is limited to 2400 volts.

    Approvals - MV90 2.4kV Non-Shielded:    

    UL listed as MV-90  Wet and Dry    
    UL1072                                                               
    ICEA S-96-659/NEMA WC71:                          
    Non-shielded cables 2001 to 5000 volts for
    electrical energy distribution            

       

    Construction - MV90 2.4kV Non-Shielded:

    • Stranded, soft annealed bare copper conductor  
    • (Aluminum conductor available upon request)    
    • Semi-conducting cross-linked polyethylene (XLPE) conductor shield
    • Black sunlight and track resistant thermoset cross-linked Polyethylene (XLPE) insulation

    ROHS stand compliant

    All specifications are provided for reference only. Specifications will vary between manufacturers and are subject to change without notice. Be sure to check with your sales rep for the most accurate and up to date information when ordering.