Toggle Nav
rfq-icon
Toggle Nav

MV105 35kV Copper Tape Shield, EPR Insulated, CPE Jacketed

12 Items

Set Descending Direction

MV105 35kV Copper Tape Shield, EPR Insulated, CPE Jacketed

Download Spec Sheet                                                 More info!

Share

    Sycor Part No AWGStrandingConductor Diameter (in)TempVoltage RatingUL Style100% NOM. Diam. Over Insul.100% Jacket Thickness100% Approx Weight Copper100% Approx Weight Alum.133% NOM. Diam. Over Insul.133% Jacket Thickness133% Appr. O.D (in)133% Approx Weight Copper133% Approx Weight Alum.
    MV105C35KT100-1/0 1/0190.34105°C35kV10721.088011659381.23801.5213611135
    MV105C35KT100-2/0 2/0190.38105°C35kV10721.1280128810021.27801.5614901204
    MV105C35KT100-3/0 3/0190.42105°C35kV10721.1680144110811.32801.6116491288
    MV105C35KT100-4/0 4/0190.48105°C35kV10721.2180162711721.37801.6618421387
    MV105C35KT100-250 250 MCM370.52105°C35kV10721.2780179912611.421101.7821301592
    MV105C35KT100-300 300 MCM370.57105°C35kV10721.3280200113571.471101.8323411697
    MV105C35KT100-350 350 MCM370.62105°C35kV10721.3780220114481.521101.8725501797
    MV105C35KT100-400 400 MCM370.66105°C35kV10721.41110250516451.561101.9528051945
    MV105C35KT100-500 500 MCM370.74105°C35kV10721.49110289418191.641102.0332062131
    MV105C35KT100-600 600 MCM610.81105°C35kV10721.57110334520541.731102.1136182327
    MV105C35KT100-750 750 MCM610.91105°C35kV10721.67110390822951.821102.2141942581
    MV105C35KT100-1000 1000 MCM611.06105°C35kV10721.82110484126911.971102.3651452995

    12 Items

    Set Descending Direction

    Available in 100% and 133% insulation levels.  Please contact us to enquire.

    Download Spec Sheet   

     MV105 EPR Insulated, CPE Jacketed 35kV Copper Tape Shield   

    Description - MV105 35kV Copper Tape Shield:

    The MV105 35kV Copper Tape Shield is a designated medium voltage shielded power cable.

    Approvals - MV105 35kV Copper Tape Shield:

    UL listed as MV-105.
    UL 1072
    ICEA S-93-639/NEMA WC 74
    ICEA S-97-682
    AEIC CS8

       

    Construction - MV105 35kV Copper Tape Shield:

    • Soft annealed bare copper conductor, Class B per ASTM B496
    • Semi-conducting cross-linked polyethylene (XLPE) conductor shield.
    • Thermoset ethylene-propylene rubber (EPR) insulation.
    • XLPE Insulation shield
    • Soft annealed bare copper tape, 5 mil thick, 25% minimum overlap + suitable binder tape.
    • Oil Resistant, Black flame retardant thermosetting chlorinated polyethylene (CPE) compound jacket.

    Application - MV105 35kV Copper Tape Shield:

    The MV105 35kV Copper Tape Shield cable is typically used for primary power and distribution circuits in industrial and commercial installations. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends. Power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry locations, installed in cable trays, raceways, ducts and open-air, aerially or directly buried as permitted by NEC.

     

    Temperature Rating - MV105 35kV Copper Tape Shield:

    105°C – Normal Operating Temperature.

       

    Voltage Rating - MV105 35kV Copper Tape Shield:

    35kV 100% and 133% IL

    ROHS stand compliant

    All specifications are provided for reference only. Specifications will vary between manufacturers and are subject to change without notice. Be sure to check with your sales rep for the most accurate and up to date information when ordering.