Toggle Nav
rfq-icon
mobile icon
Close
  • Menu
  • Setting

MV-105 EPR Insulated, CPE Jacketed 35 kV Copper Tape Shielded

12 Items

per page
Set Descending Direction

MV-105 EPR Insulated, CPE Jacketed 35 kV Copper Tape Shielded

    Sycor Part No AWGStrandingTempVoltage RatingUL StyleConductor Diameter (in)100% NOM. Diam. Over Insul.100% Jacket Thickness100% Approx Weight Copper100% Approx Weight Alum.133% NOM. Diam. Over Insul.133% Jacket Thickness133% Appr. O.D (in)133% Approx Weight Copper133% Approx Weight Alum.
    MV105C35KT100-1/0 1/019105°C35kV10720.341.088011659381.23801.5213611135
    MV105C35KT100-2/0 2/019105°C35kV10720.381.1280128810021.27801.5614901204
    MV105C35KT100-3/0 3/019105°C35kV10720.421.1680144110811.32801.6116491288
    MV105C35KT100-4/0 4/019105°C35kV10720.481.2180162711721.37801.6618421387
    MV105C35KT100-250 25037105°C35kV10720.521.2780179912611.421101.7821301592
    MV105C35KT100-300 30037105°C35kV10720.571.3280200113571.471101.8323411697
    MV105C35KT100-350 35037105°C35kV10720.621.3780220114481.521101.8725501797
    MV105C35KT100-400 40037105°C35kV10720.661.41110250516451.561101.9528051945
    MV105C35KT100-500 50037105°C35kV10720.741.49110289418191.641102.0332062131
    MV105C35KT100-600 60061105°C35kV10720.811.57110334520541.731102.1136182327
    MV105C35KT100-750 75061105°C35kV10720.911.67110390822951.821102.2141942581
    MV105C35KT100-1000 100061105°C35kV10721.061.82110484126911.971102.3651452995

    12 Items

    per page
    Set Descending Direction

    Available in 100% and 133% insulation levels.  Please contact us to enquire.

    Download Spec Sheet

         


    Description - MV-105 EPR Insulated, CPE Jacketed 35 kV Copper Tape Shielded:

    Medium voltage shielded power cable.

       

    Approvals - MV-105 EPR Insulated, CPE Jacketed 35 kV Copper Tape Shielded:

    UL listed as MV-105.
    UL 1072
    ICEA S-93-639/NEMA WC 74
    ICEA S-97-682
    AEIC CS8

       

    Construction - MV-105 EPR Insulated, CPE Jacketed 35 kV Copper Tape Shielded:

    • Soft annealed bare copper conductor, Class B per ASTM B496
    • Semi conducting cross-linked polyethylene (XLPE) conductor shield.
    • Thermoset ethylene propylene rubber (EPR) insulation.
    • XLPE Insulation shield
    • Soft annealed bare copper tape, 5 mil thick, 25% minimum overlap + suitable binder tape.
    • Oil Resistant, Black flame retardant thermosetting chlorinated polyethylene (CPE) compound jacket.

    Temperature Rating - MV-105 EPR Insulated, CPE Jacketed 35 kV Copper Tape Shielded:

    105°C – Normal Operating Temperature.

      

    Voltage Rating - MV-105 EPR Insulated, CPE Jacketed 35 kV Copper Tape Shielded:

    35kV 100% and 133% IL

      

    Application - MV-105 EPR Insulated, CPE Jacketed 35 kV Copper Tape Shielded:

    Primary power and distribution circuits in industrial and commercial installations. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.
    Power circuits in generating plants where line to ground fault current are within shield capabilities.
    May be used in wet or dry locations, installed in cable trays, raceways, duct and open air, aerially or directly buried as permitted by NEC.

    All specifications are provided for reference only. Specifications will vary between manufacturers and are subject to change without notice. Be sure to check with your sales rep for the most accurate and up to date information when ordering.