Jumper Cable - 5kv / 15kv, Non-Shielded
Jumper Cable - 5kv / 15kv, Non-Shielded
Sycor Part No | AWG | Stranding | Insulation Thickness (In) | Nom. O.D. (In) | Jacket Thickness (In) | Temp | Voltage Rating | Approx Weight LBS./MFT | Ampacity | |
---|---|---|---|---|---|---|---|---|---|---|
JUM02259-2 | 2 | 259 x 0.0159 | .175 | .820 | .080 | 90°C | 15kv | 480 | 195 |
|
JUM1/0414-2 | 1/0 | 414 x 0.0159 | .175 | .905 | .080 | 90°C | 15kv | 689 | 255 |
|
JUM2/0522-2 | 2/0 | 522 x 0.0159 | .175 | .997 | .080 | 90°C | 15kv | 747 | 293 |
|
JUM4/0829-2 | 4/0 | 829 x 0.0159 | .175 | 1.140 | .080 | 90°C | 15kv | 1051 | 389 |
|
JUM3501361-2 | 350 MCM | 1361 x 0.0159 | .175 | 1.305 | .080 | 90°C | 15kv | 1584 | 543 |
|
JUM5001921-2 | 500 MCM | 1921 x 0.0159 | .175 | 1.410 | .080 | 90°C | 15kv | 2082 | 678 |
|
Additional strandings and gauges available upon request. Please contact us to enquire.
Description of Jumper Cable:
Sycor’s jumper cable is made with flexible rope lay conductor and EPR insulation. Sycor jumper cable excels in power distribution and high voltage applications.
Temperature Rating of Jumper Cable:
90°C
Construction of Jumper Cable:
Flexible stranded tinned copper
Ethylene propylene rubber (EPR) insulation
Red CPE thermoset jacket
Synthetic semi-conducting tape separator (between conductor & insulation)
Approvals of Jumper Cable:
ASTM B3, B173
Voltage Rating of Jumper Cable:
5kv / 15kv
Application of Jumper Cable:
Sycor’s jumper cable is typically used for power leads near portions of aerial power lines. Jumper cables are reliable for high voltage applications where a non-shielded cable is required.
Colour options for Jumper Cable:
Value-Added Services for Jumper Cable:
All specifications are provided for reference only. Specifications will vary between manufacturers and are subject to change without notice. Be sure to check with your sales rep for the most accurate and up to date information when ordering.