MV-105 EPR Insulated, CPE Jacketed 25 kV Copper Tape Shielded

    Sycor Part No AWGStrandingTempVoltage RatingUL StyleConductor Diameter (in)100% NOM. Diam. Over Insul.100% Jacket Thickness100% Approx Weight Copper100% Approx Weight Alum.133% NOM. Diam. Over Insul.133% Jacket Thickness133% Appr. O.D (in)133% Approx Weight Copper133% Approx Weight Alum.
    MV105C25KT100-1 119105°C25kV10720.300.8680844664-----
    MV105C25KT100-1/0 1/019105°C25kV10720.340.90809417141.02801.321103877
    MV105C25KT100-2/0 2/019105°C25kV10720.380.948010597721.06801.361225939
    MV105C25KT100-3/0 3/019105°C25kV10720.420.998012048431.11801.4013761016
    MV105C25KT100-4/0 4/019105°C25kV10720.481.048014089531.16801.4515601105
    MV105C25KT100-250 25037105°C25kV10720.521.1080157110341.22801.5117291192
    MV105C25KT100-300 30037105°C25kV10720.571.1580176711221.27801.5619301285
    MV105C25KT100-350 35037105°C25kV10720.621.1980196012071.31801.6121281374
    MV105C25KT100-400 40037105°C25kV10720.661.2480214912891.36801.6523221462
    MV105C25KT100-500 50037105°C25kV10720.741.3180254314471.431101.7928121737
    MV105C25KT100-600 60061105°C25kV10720.811.40110301117201.521101.9132581967
    MV105C25KT100-750 75061105°C25kV10720.911.49110355819451.621102.0038172204
    MV105C25KT100-1000 100061105°C25kV10721.061.65110451923691.771102.1647432593

    13 Items

    per page
    Set Descending Direction

    *Available in 100% and 133% Insulation Levels.  

    Download Spec Sheet

         


    Description - MV-105 EPR Insulated, CPE Jacketed 25 kV Copper Tape Shielded:

    Medium voltage shielded power cable.

      

    Approvals - MV-105 EPR Insulated, CPE Jacketed 25 kV Copper Tape Shielded:

    UL listed as MV-105.
    UL 1072
    ICEA S-93-639/NEMA WC 74
    ICEA S-97-682
    AEIC CS8

      

    Construction - MV-105 EPR Insulated, CPE Jacketed 25 kV Copper Tape Shielded:

    • Soft annealed bare copper conductor, Class B per ASTM B496
    • Semi conducting cross-linked polyethylene (XLPE) conductor shield.
    • Thermoset ethylene propylene rubber (EPR) insulation.
    • XLPE Insulation shield
    • Soft annealed bare copper tape, 5 mil thick, 25% minimum overlap + suitable binder tape.
    • Oil Resistant, Black flame retardant thermosetting chlorinated polyethylene (CPE) compound jacket.

    Temperature Rating - MV-105 EPR Insulated, CPE Jacketed 25 kV Copper Tape Shielded:

    105°C – Normal Operating Temperature.

      

    Voltage Rating - MV-105 EPR Insulated, CPE Jacketed 25 kV Copper Tape Shielded:

    25kV 100% and 133% IL

      

    Application - MV-105 EPR Insulated, CPE Jacketed 25 kV Copper Tape Shielded:

    Primary power and distribution circuits in industrial and commercial installations. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.
    Power circuits in generating plants where line to ground fault current are within shield capabilities.
    May be used in wet or dry locations, installed in cable trays, raceways, duct and open air, aerially or directly buried as permitted by NEC.