MV-105 EPR Insulated, CPE Jacketed 5 kV Copper Tape Shielded

14 Items

per page
Set Descending Direction

MV-105 EPR Insulated, CPE Jacketed 5 kV Copper Tape Shielded

    Sycor Part No AWGStrandingTempVoltage RatingUL StyleConductor Diameter (in)100% Insulation Thickness100% Jacket Thickness100% Approx Weight Copper100% Approx Weight Alum.133% Insulation Thickness133% Jacket Thickness133% Appr. O.D (in)133% Approx Weight Copper133% Approx Weight Alum.
    MV105C5KT100-6 67105°C5kV10720.170.39602672110.39600.61267211
    MV105C5KT100-4 47105°C5kV10720.210.43603362460.43600.66336246
    MV105C5KT100-2 27105°C5kV10720.270.49604382960.49600.71438293
    MV105C5KT100-1 119105°C5kV10720.300.52605053250.52600.74505325
    MV105C5KT100-1/0 1/019105°C5kV10720.340.55605903630.55600.78590363
    MV105C5KT100-3/0 3/019105°C5kV10720.420.64808615000.64800.91861500
    MV105C5KT100-250 25037105°C5kV10720.520.758011706330.75801.021170633
    MV105C5KT100-300 30037105°C5kV10720.570.808013507060.80801.071350706
    MV105C5KT100-350 35037105°C5kV10720.620.858015297770.85801.111529777
    MV105C5KT100-400 40037105°C5kV10720.660.898017068490.89801.161706849
    MV105C5KT100-500 50037105°C5kV10720.740.978020559810.97801.232055981
    MV105C5KT100-600 60061105°C5kV10720.811.0580243611461.05801.3424361146
    MV105C5KT100-750 75061105°C5kV10720.911.1580295013391.15801.4429501339
    MV105C5KT100-1000 100061105°C5kV10721.061.3080380416571.30801.5938041657

    14 Items

    per page
    Set Descending Direction

    Available in 100% and 133% insulation levels. Please contact us to enquire.

    Download Spec Sheet

        


    Description - MV-105 EPR Insulated, CPE Jacketed 5 kV Copper Tape Shielded:

    Medium voltage shielded power cable.

       

    Approvals - MV-105 EPR Insulated, CPE Jacketed 5 kV Copper Tape Shielded:

    UL listed as MV-105                          
    UL 1072                                                               
    ICEA S-93-639/NEMA WC74:          
    Shielded power cables 5,000 to 46,000V     
    ICEA S-97-682: utility                        
    Shielded power cables 5,000 to 46,000V
    AEIC CS8: extruded dielectric shielded
    Power cables 5,000 to 46,000V

       

    Construction - MV-105 EPR Insulated, CPE Jacketed 5 kV Copper Tape Shielded:

    • Stranded, soft annealed bare copper conductor
    • (Aluminum conductor available upon request)            
    • Semi-conducting cross-linked polyethylene (XLPE) conductor shield
    • Thermoset Ethylene Propylene Rubber (EPR) insulation
    • Semi-conducting cross-linked Polyethylene (XLPE) insulation shield
    • Soft annealed bare copper tape (5 mil thickness) 25% overlap, binder tape
    • Black oil resistant and flame retardant thermoset Chlorinated Polyethylene (CPE) jacket

    Temperature Rating - MV-105 EPR Insulated, CPE Jacketed 5 kV Copper Tape Shielded: 

    105°C – Normal Operating Temperature.

       

    Voltage Rating - MV-105 EPR Insulated, CPE Jacketed 5 kV Copper Tape Shielded:

    5kV 100% and 133% IL

       

    Application - MV-105 EPR Insulated, CPE Jacketed 5 kV Copper Tape Shielded:

    Primary power and distribution circuits in industrial and commercial installations
    Power circuits in generating plants where line to ground fault current are within shield capabilities.
    May be used in wet or dry locations, installed in cable trays, raceways, duct and open air, aerially or directly buried as permitted by NEC.

    All specifications are provided for reference only. Specifications will vary between manufacturers and are subject to change without notice. Be sure to check with your sales rep for the most accurate and up to date information when ordering.