Toggle Nav
rfq-icon
mobile icon
Close
  • Menu
  • Setting

MV-105 EPR Insulated, PVC Jacketed 8 kV Copper Tape Shielded

16 Items

per page
Set Descending Direction

MV-105 EPR Insulated, PVC Jacketed 8 kV Copper Tape Shielded

    Sycor Part No AWGStrandingTempVoltage RatingUL StyleConductor Diameter (in)100% NOM. Diam. Over Insul.100% Jacket Thickness100% Approx Weight Copper100% Approx Weight Alum.133% NOM. Diam. Over Insul.133% Jacket Thickness133% Appr. O.D (in)133% Approx Weight Copper133% Approx Weight Alum.
    MV1058KT100-6 67105°C8kV10720.170.44602912340.49600.71324267
    MV1058KT100-4 47105°C8kV10720.210.48603612710.53600.75395306
    MV1058KT100-2 27105°C8kV10720.270.54604653220.59600.80502359
    MV1058KT100-1 119105°C8kV10720.300.57605323520.62800.88605425
    MV1058KT100-1/0 1/019105°C8kV10720.340.61606183920.66800.91694468
    MV1058KT100-2/0 2/019105°C8kV10720.380.61807604730.70800.95803517
    MV1058KT100-3/0 3/019105°C8kV10720.420.65808335320.74801.00938577
    MV1058KT100-4/0 4/019105°C8kV10720.480.748010576020.80801.051104650
    MV1058KT100-250 25037105°C8kV10720.520.808012056670.85801.111255718
    MV1058KT100-300 30037105°C8kV10720.570.858013867420.90801.161439794
    MV1058KT100-350 35037105°C8kV10720.620.908015678140.95801.201621868
    MV1058KT100-400 40037105°C8kV10720.660.948017448850.99801.251801941
    MV1058KT100-500 50037105°C8kV10720.741.0280212210471.07801.3521821107
    MV1058KT100-600 60061105°C8kV10720.811.1080248011891.15801.4325441253
    MV1058KT100-750 75061105°C8kV10720.911.2080299713841.25801.5330651452
    MV1058KT100-1000 100061105°C8kV10721.061.3580385517051.401101.7440331883

    16 Items

    per page
    Set Descending Direction

    *Available in 100% and 133% Insulation Levels. 
    Cables that comply with 8 kV 100% can be marked 5K 133%.

    Download Spec Sheet

      

    Description - MV-105 EPR Insulated, PVC Jacketed 8 kV Copper Tape Shielded:

    Medium voltage shielded power cable.

      

    Approvals - MV-105 EPR Insulated, PVC Jacketed 8 kV Copper Tape Shielded:

    ICEA S-93-639/NEMA WC 74
    ICEA S-97-682
    AEIC CS8
    UL listed as MV-105.
    UL 1072

     

    Construction - MV-105 EPR Insulated, PVC Jacketed 8 kV Copper Tape Shielded:

    • Soft annealed bare copper conductor, Class B per ASTM B496.
    • Semi conducting cross-linked polyethylene (XLPE) conductor shield.
    • Thermoset ethylene propylene rubber (EPR) insulation.
    • SC XLPE insulation shield.
    • Copper tape 5 mil thick 25% minimum overlap metallic shield.
    • Oil Resistant, black sunlight resistance and flame retardant polyvinyl chloride (PVC) jacket.

    Temperature Rating - MV-105 EPR Insulated, PVC Jacketed 8 kV Copper Tape Shielded:

    105°C Normal Operating Temperature

       

    Voltage Rating - MV-105 EPR Insulated, PVC Jacketed 8 kV Copper Tape Shielded:

    8 kV 100% and 133% IL

       

    Application - MV-105 EPR Insulated, PVC Jacketed 8 kV Copper Tape Shielded:

    Primary power and distribution circuits in industrial and commercial installations. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.
    Power circuits in generating plants where line to ground fault current are within shield capabilities.
    May be used in wet or dry locations, installed in cable trays, raceways, duct and open air, aerially or directly buried as permitted by NEC.

    All specifications are provided for reference only. Specifications will vary between manufacturers and are subject to change without notice. Be sure to check with your sales rep for the most accurate and up to date information when ordering.