MV105 35kV Copper Tape Shield, EPR Insulated, PVC Jacketed

12 Items

Set Descending Direction

MV105 35kV Copper Tape Shield, EPR Insulated, PVC Jacketed

Download Spec Sheet                                                 More info!

Share

    Sycor Part No AWGStrandingConductor Diameter (in)TempVoltage RatingUL Style100% NOM. Diam. Over Insul.100% Jacket Thickness100% Approx Weight Copper100% Approx Weight Alum.133% NOM. Diam. Over Insul.133% Jacket Thickness133% Appr. O.D (in)133% Approx Weight Copper133% Approx Weight Alum.
    MV10535KT100-1/0 1/0190.34105°C35kV10721.088011479201.23801.5113411115
    MV10535KT100-2/0 2/0190.38105°C35kV10721.128012709841.27801.5514701184
    MV10535KT100-3/0 3/0190.42105°C35kV10721.1680142210611.32801.6016281267
    MV10535KT100-4/0 4/0190.48105°C35kV10721.2180160711531.37801.6518201365
    MV10535KT100-250 250 MCM370.52105°C35kV10721.2780177812411.421101.7621031565
    MV10535KT100-300 300 MCM370.57105°C35kV10721.3280198013351.471101.8123141669
    MV10535KT100-350 350 MCM370.62105°C35kV10721.3780217914261.521101.8625221769
    MV10535KT100-400 400 MCM370.66105°C35kV10721.41110247916191.561101.9422761916
    MV10535KT100-500 500 MCM370.74105°C35kV10721.49110286717911.641102.0131762100
    MV10535KT100-600 600 MCM610.81105°C35kV10721.57110331520251.731102.1035862296
    MV10535KT100-750 750 MCM610.91105°C35kV10721.67110387722641.821102.1941612548
    MV10535KT100-1000 1000 MCM611.06105°C35kV10721.82110480826581.971102.3551102960

    12 Items

    Set Descending Direction

    *Available in 100% and 133% Insulation Levels. 

    Download Spec Sheet    

    MV105 EPR Insulated, PVC Jacketed 35kV Copper Tape Shield 

    Description - MV105 35kV Copper Tape Shield:

    The MV105 35kV copper tape shield is a medium voltage shielded power cable.

    Approvals - MV105 35kV Copper Tape Shield:

    ICEA S-93-639/NEMA WC 74
    ICEA S-97-682
    AEIC CS8
    UL listed as MV-105.
    UL 1072

       

    Construction - MV105 35kV Copper Tape Shield:

    • Soft annealed bare copper conductor, Class B per ASTM B496.
    • Semi-conducting cross-linked polyethylene (XLPE) conductor shield.
    • Thermoset ethylene-propylene rubber (EPR) insulation.
    • SC XLPE insulation shield.
    • Copper tape 5 mil thick 25% minimum overlap metallic shield.
    • Oil Resistant, black sunlight resistance and flame retardant polyvinyl chloride (PVC) jacket.

    Application - MV105 35kV Copper Tape Shield:

    The MV105 35kV Copper Tape Shield is typically used for primary power and distribution circuits in industrial and commercial installations. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends. Power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry locations, installed in cable trays, raceways, ducts and open-air, aerially or directly buried as permitted by NEC.


    Temperature Rating - MV105 35kV Copper Tape Shield:

    105°C Normal Operating Temperature

       

    Voltage Rating - MV105 35kV Copper Tape Shield:

    35 kV 100% and 133% IL

    ROHS stand compliant

    All specifications are provided for reference only. Specifications will vary between manufacturers and are subject to change without notice. Be sure to check with your sales rep for the most accurate and up to date information when ordering.